All installations and services must be performed by qualified service personnel.

37

While ignition electrodes

are sparking does fuel

valve open?

No

Yes

Yes

Yes

Check wiring to fuel valve.

If valve does not open,

replace fuel valve.

Yes

No

No

No

After pre-purge, does the

ignition control (GMD) or

the oil primary (OMD)

produce a spark at the

ignition electrodes?

Is there 24 VAC across the power

terminals of the ignition control

module (GMD) or 120 VAC across

the ignition transformer (OMD)?

On the GMD,has the burner

motor centrifugal switch

closed? If 120 VAC is

measured across the switch,

replace the burner motor. Else,

replace thermostat. On the OMD,

try resetting the oil primary

control by depressing the

RESET button. Check cad cell

function. If all else fails,

replace the oil primary.

Check wiring to the electrodes and

ignition control module fuse (GMD)

or the ignition transformer and the

electrodes (OMD). Also, check ignition

electrode gap. Reset if necessary.

Replace electrodes, ignition control

module (GMD) or ignition transformer (OMD).

Is there 24 VAC (GMD) across

"MV" terminals on ignition

control module during ignition

attempt. Does the oil solenoid

valve have 120 VAC across it

during the ignition attempt (OMD)?

On the GMD, reset the module

by interrupting power to system

for more than one second. If this

does not work, replace ignition

control module. On the OMD, try

resetting the oil primary control

by depressing the RESET button.

If this does not work, replace the

oil primary.