Thermo Pride OMD-70 User Manual

Page 36

Advertising
background image

All installations and services must be performed by qualified service personnel.

Yes

Set thermostat subbase to "HEAT"

Does thermostat make contact?

Does a "call for

heat" initiate an

ignition cycle?

No

Yes

Is room temperature

above 90 deg. F?

Yes

Wait for room air to cool.

Yes

Turn thermostat setting

above room temp.

Replace thermostat

Is there 120 VAC

across lines L1 & L2?

Check input power. Reset circiut

breaker, or replace blown fuse in

disconnected switch.

No

Have either of the

high limit thermostats

activated?

No

Yes

No

Yes

Turn power

switch "on".

Wait for furnace to cool.

Look for cause(s) of high

limit activation,eg. low

airflow, over-firing,

blocked flue,etc..

Correct any

abnormal conditions.

No

No

Yes

Yes

No

Is the power switch "off"?

No

Is room temperature above

thermostat setting?

With power on,measure

voltage across the aux.

high limit thermostat N.C.

contact to L2. If not 120 VAC,

replace aux. high limit

thermostat. Else,replace

high limit thermostat.

Is the control transformer

(GMD) or oil primary control

(OMD) receiving 120 VAC?

OMD/GMD TROUBLESHOOTING FLOWCHART

Note: Check diagnostic code through view port

prior to removing doors.

35