When the environmental conditions preclude the “3P” measurement mode, as for example
in a city center. In TT plants it is possible to measure the earth resistance with the
simplified “2P” method that gives a higher value than the “3P” mode does.
An auxiliary rod is necessary; it must have an insignificant earth resistance and must be
independent of the earth plant under test.
In the picture above, a water tube is used as the auxiliary rod. But, any metallic object
fixed to the ground could replace it.

Example: if the operator takes three consecutive measurements, the instrument displays

1

st

measurement:

main display = measured resistance value (Ex: 0.90

Ω)

secondary display on the left-hand side = 001 (no. of measurements = 1
means that 1 earth measurement has been taken)
secondary display = average of the measurements taken (in case just one
measurement has been taken the medium value is equal to the measured
value, in this case 0.90

Ω)

2

nd

measurement:

main display = measured resistance value (Ex: 0.96

Ω)

secondary display = average of the measurements taken ((Val1+Val2)/no.
of measurements = (0.90+0.96)/2 = 0.93

Ω)

3

rd

measurement:

main display = measured resistance value (Ex: 0.93

Ω)

secondary display = average of the measurements taken ((Val1+Val2)/no.
of measurements = (0.90+0.96+0.93)/3 = 0.93

Ω)



Note: Any test with a result over 1999

Ω is not inserted in the calculation of medium

value.



Example: 1

st

measurement:

main display: 1.07

secondary display: 1.07

2

nd

measurement

main display: 4.15

secondary display: 2.61

3

rd

measurement (not inserted in the medium value)

main display: >1999

secondary display: 2.61