11. PRACTICAL REPORTS FOR ELECTRICAL TESTS

11.1. LOW

: CONTINUITY MEASUREMENT ON PROTECTIVE CONDUCTORS

PURPOSE OF THE TEST
Check the continuity of:
a) Protective conductors (PE), main equalizing potential conductors (EQP), secondary

equalizing potential conductors (EQS) in TT and TN-S systems.

b) Neutral conductors having functions of protective conductors (PEN) in TN-C system.

NOTE: This test is to be preceded by a visual check verifying the existence of yellow-

green protective and equalizing potential conductors as well as compliance of the
sections used with the standards’ requirements.


INSTALLATION PARTS TO BE CHECKED

Connect one of the
test leads to the
protective
conductor of the
FM socket and the
other to the
equalizing potential
node of the earth
installation.

Connect one of the
test leads to the
external mass (in
this case the water
pipe) and the other
to the earth
installation using
for example the
protective
conductor of the
closest FM socket.

Examples for continuity measurement on conductors