Reference

MVI71-DFNT ♦ PLC 5

User Manual

EtherNet/IP Client/Server Communication Module

Page 110 of 175

ProSoft Technology, Inc.

February 3, 2011

5.8 Configuration Data

This section contains a listing of the parameters and their definitions for the

MVI71-DFNT module configuration.

[Section]/Item

Value

Range

Description

[MODULE]

Configuration header for general module

information

Module Name:

Up to 80 chars Name of the module for use on reports. Use this

parameter to identify your module in your system.

Read Register

Start:

0 to 3999

This parameter specifies the starting register in the

module where data will be transferred from the

module to the processor. Valid range for this

parameter is 0 to 3999.

Read Register

Count:

0 to 3960

This parameter specifies the number of registers to

be transferred from the module to the processor.

Valid entry for this parameter is 0 to 3960.

Write Register

Start:

0 to 3999

This parameter specifies the starting register in the

module where the data transferred from the

processor will be placed. Valid range for this

parameter is 0 to 3999.

Write Register

Count:

0 to 3960

This parameter specifies the number of registers to

transfer from the processor to the module. Valid

entry for this parameter is 0 to 3960.

Failure Flag Count:

0 to 65535

This parameter specifies the number of successive

transfer errors that must occur before the

communication ports are shut down. If the

parameter is set to 0, the communication ports will

continue to operate under all conditions. If the value

is set larger than 0 (1 to 65535), communications

will cease if the specified number of failures occur.

Initialize Output

Data:

0 or 1

This parameter determines if the output data for the

module should be initialized with values from the

processor. If the value is set to 0, the output data

will be initialized to 0. If the value is set to 1, the

data will be initialized with data from the processor.

Use of this option requires associated ladder logic

to pass the data from the processor to the module.

DFNT Server File

Size

100 or 1000

Sets the maximum file size (100 or 1000) for the

servers

[Section]/Item

Value

Range

Description

[DF1 Pass-Through Server Port 1]

Start header for the pass-through server

Enabled:

Y or N

This parameter determines if the pass-through

server will be utilized.

Server Port

Number:

1 to 65535

Service port number to be associated with this

server. The number assigned must match that used

by the client software to establish the connection.

Busy Timeout:

100 to 65535

milliseconds

This parameter sets the number of milliseconds the

server will wait for the pass-through port to become

available. Valid data range for this parameter is 100

to 65535.