ProSoft Technology MVI71-DFNT User Manual
Page 142

Reference
MVI71-DFNT ♦ PLC 5
User Manual
EtherNet/IP Client/Server Communication Module
Page 142 of 175
ProSoft Technology, Inc.
February 3, 2011
Next, add items to the client. The following shows an example dialog used to add
a floating-point data item:
It is important to set the Access Path value to the Topic name assigned in
RSLinx and to set the Item Name to a valid controller tag in the DFNT module.
The Datatype parameter must be set to match that of the controller tag. In the
example shown, the VT_R4 data type is selected for the floating-point tag. The
Validate button can be used to verify that the point is valid in the OPC server.
After configuring the new data item, click OK to add the point. The following
illustration shows the new item and event windows.