Operation, Enable the power-saving function, Disable the power-saving function – APC Power-Saving Back-UPS Pro 1500 International Version (230V) User Manual

Page 3: Setting the threshold, Low sensitivity, Medium sensitivity (default), High sensitivity, 300 vac, 294 vac, 288 vac

Advertising
background image

Back-UPS Pro 1200 & 1500 230 V Installation and Operation

3

Operation

Power-Saving Function

To conserve electricity, configure the Back-UPS to recognize a Master device, such as a desktop
computer or an A/V receiver, and Controlled peripheral devices, such as a printer, speakers, or a scanner.
When the Master device goes into Sleep or Standby mode, or is switched OFF, the Controlled device(s)
will be switched off as well, saving electricity.

Enable the Power-Saving function.

Press and hold

M

UTE

and

D

ISPLAY

simultaneously for two seconds. The

Back-UPS will beep to indicate that the feature is enabled. The leaf icon on the display will illuminate.

Disable the Power-Saving function.

Press and hold

M

UTE

and

D

ISPLAY

simultaneously for two seconds. The

Back-UPS will beep to indicate that the feature is disabled. The leaf icon on the display will darken.

Setting the threshold.

The amount of power used by a device in Sleep or Standby mode varies between devices. It

may be necessary to adjust the threshold at which the Master outlet signals the Controlled outlets to shut down.

1. Ensure a master device is connected to the Master outlet. Put that device into Sleep or Standby mode, or turn it

OFF.

2. Press

D

ISPLAY

and

M

UTE

simultaneously and hold for six seconds, until the leaf icon flashes three times and the

Back-UPS beeps three times.

3. The Back-UPS will now recognize the threshold level of the Master device and save it as the new threshold setting.

Power-Saving Display

The display interface can be configured to be continuously illuminated, or to save energy, it can be configured to
darken after a period of inactivity.

1. Full Time Mode: Press and hold

DISPLAY

for two seconds. The display will illuminate and the Back-UPS will beep

to confirm the Full-Time mode.

2. Power-Saving Mode: Press and hold

DISPLAY

for two seconds. The display will darken and the Back-UPS will

beep to confirm the Power-Saving mode. While in Power-Saving Mode, the display will illuminate if a button is
pressed, it then darkens after 60 seconds of no activity.

Unit sensitivity

Adjust the sensitivity of the Back-UPS to control when it will switch to battery power; the higher the sensitivity, the
more often the Back-UPS will switch to battery power.

1. Ensure the Back-UPS is connected to utility power, but is OFF.

2. Press and hold the

P

OWER

button for six seconds. The

L

OAD

C

APACITY

bar will flash on and off, indicating that the

Back-UPS is in programming mode.

3. Press

P

OWER

again to rotate through the menu options. Stop at selected sensitivity. The Back-UPS will beep to

confirm the selection.

Low sensitivity

Medium sensitivity (Default)

High sensitivity

156-300 Vac

176-294 Vac

176-288 Vac

Input voltage is extremely low or
high. (Not recommended for
computer loads.)

The Back-UPS frequently switches to
battery power.

The connected equipment is
sensitive to voltage fluctuations.

Advertising