Installing the fireplace – Hearth and Home Technologies Everest User Manual

Page 10

Advertising
background image

Heat & Glo • Everest • 750-900 Rev. o • 10/08

10

3

Installing the Fireplace

Step 1. Locating the Fireplace

The diagram below shows space and clearance require-
ments for locating a fi replace within a room.

A

B

C

D

E

35 1/2”

21 3/4”

30 1/2”

43 1/4”

61 3/16”

(902 mm)

(552 mm) (775 mm) (1099 mm) (1554 mm)

Minimum Clearances

from the Fireplace to Combustible Materials

Inches

mm

Glass Front .........................36 ..............914
Floor

.............................0

..................0

Rear

........................... 1/2

................13

Sides

........................... 1/2

................13

Top

..........................4

1/2

............. 114

Ceiling*

............................31

...............787

Figure 2. Fireplace Dimensions, Locations, and

Space Requirements

Framing should be
constructed of 2 X 4
lumber or heavier.

A. ..... 35-1/8” (892 mm)

B. ..... 50-1/2” (1283 mm)

C. ..... 21-3/8” (542 mm)

D. ..... 55-1/2” (1372 mm)

Figure 3. Framing Dimensions

For minimum clearances, see the direct vent termination
clearance diagrams on pages 20 and 21 in this manual.

Minimum Clearances

from the Vent Pipe to Combustible Materials

Inches

mm

Vertical Sections. .............. 1 ................ 25

Horizontal Sections
Top ...................................... 3 ................. 75
Bottom ................................ 1 ................. 25
Sides................................... 1 ................. 25

At Wall Firestops
Top ...................................... 3 ................. 76
Bottom ................................ 1 ................. 25
Sides................................... 1 ................. 25

A

B

4” (102 mm)

D

C

E

1/2” (13 mm)

Shows center of

10” x 12” vent framing

holes for venting.

C

B

A

D

* The clearance to the ceiling is measured from the

top of the unit, excluding the stand-offs and collar.
See Figure 24 for further details.

(Center of 12 x 10)

Clearance Requirements

The top, back, and sides of the fi replace are defi ned by
stand-offs. The minimum clearance to a perpendicular wall
extending past the face of the fi replace is 4 inches (102
mm). The back of the fi replace may be recessed 23 (584
mm) inches (546 mm) into combustible construction.

Step 2. Framing the Fireplace

Fireplace framing can be built before or after the fi replace is
set in place. Framing should be positioned to accommodate
wall coverings and fi replace facing material. The diagram
below shows framing reference dimensions.

CAUTION: MEASURE FIREPLACE DIMENSIONS, AND
VERIFY FRAMING METHODS AND WALL COVERING
DETAILS, BEFORE FRAMING.

The distance from the unit to combustible construction is
to be measured from the unit outer wrap surface to the
combustible construction, NOT from the screw heads
that secure the unit together.