For vertical runs – Hearth and Home Technologies Everest User Manual

Page 18

Advertising
background image

Heat & Glo • Everest • 750-900 Rev. o • 10/08

18

For Vertical Runs

- One ceiling fi restop is REQUIRED

at the hole in each ceiling through which the vent
passes.

To install fi restops for vertical runs that pass through
ceilings:

• Position a plumb bob directly over the center of the verti-

cal vent component.

• Mark the ceiling to establish the centerpoint of the

vent.

• Drill a hole or drive a nail through this centerpoint.

• Check the fl oor above for any obstructions, such as wir-

ing or plumbing runs.

• Reposition the fi replace and vent system, if necessary,

to accommodate the ceiling joists and/or obstructions.

• Cut a 10 inch x 10 inch (254 mm x 254 mm) hole through

the ceiling, using the centerpoint previously marked.

• Frame the hole with framing lumber the same size as

the ceiling joists.

Figure 15. Ceiling Firestop (Ceiling Side)

If the area above the ceiling is NOT an attic, position
and secure the ceiling fi restop on the ceiling side of the
previously cut and framed hole.

This shows a ceiling installation.

Figure 14. 10” x 10” Hole & New Framing Members

If the area above the ceiling IS an attic, position and secure
the fi restop on top of the previously framed hole.

This shows an attic installation. Keep insulation away from
the vent pipe at least 1 inch (25 mm).

Figure 16. Attic Firestop

JOIST

CEILING FIRESTOP

CEILING

NAILS (4 REQUIRED)

JOIST

CEILING FIRESTOP

CEILING

NAILS (4 REQUIRED)

CEILING

NEW
FRAMING
MEMBERS

EXISTING CEILING
JOISTS

CHIMNEY
HOLE

10" (25.4 cm)

)

m

c

4

.

5

2

(

0

1

Figure 13. 10” x 12” Hole and Vent Pipe

To install fi restops for horizontal runs that pass through
either interior or exterior walls:

• Cut a 12 inch by 10 inch (305 mm X 254 mm) hole

through the wall. The center of the hole is one (1) inch
(25.4 mm) above the center of the horizontal vent
pipe.

• Position

the

fi restops on both sides of the hole previously

cut and secure the fi restops with nails or screws.

• The pipe opening of the fi restops MUST be placed

towards the bottom of the fi replace.

NOTE: There must be NO INSULATION or other
combustibles inside the framed fi restop opening.

10" (25.4 cm)

12" (30.5 cm)

INTERIOR

WALL SHIELD

NOTE: There must be NO INSULATION or other
combustibles inside the framed fi restop opening.

Advertising