4.3

Wiring ST 3000 Transmitter,

Continued

Approval body
requirements

If your transmitter was ordered with Table III option 3N for self-
declared approval per 94/9/EC (ATEX4), you must use a power supply
that includes a voltage limiting device that will keep the voltage to the
transmitter from exceeding 42 Vdc. You can achieve this by using a
battery as the supply or one of these voltage limiting means.
• Double wound mains transformer per BS 3535 or equivalent.
• An adequately rated zener diode whose voltage is not significantly

higher than the rated voltage.

• An adequately rated semiconductor voltage regulator.

Lightning protection

When your transmitter is equipped with optional lightning protection,
you must connect a wire from the transmitter to ground as shown in
Figure 15 to make the protection effective. We recommend that you use
a size 8 (American Wire Gage) or (8.37mm

2

) bare or green covered

wire.

Figure 15

Ground Connection for Lightning Protection.

Electronics

Housing

Connect to

Earth Ground

Continued on next page

42

ST 3000 Release 300 Installation Guide