T7300D SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTAT

Table 2. Thermostat Installer Setup Options (Continued).

(continued)

Installer Setup

Number

(Press

Unoccupied

Temp key

Factory-Setting

Other Choices

(Press

or

key to change)

Actual

Select

to change)

Display

Description

Display

Description

Setting

Cooling cycle

9

4

Stage 1—4 cph

3

3—3 cph

rate

10

4

Stage 2—4 cph

11

4

Stage 3—4 cph

System setting
adjustment
(models with
System key)

12

Depends
on model

System selection

0, 1 or 2

0—System setting key is

operational

1—Auto setting is disabled
2—Auto only setting

Degree tempera-
ture display

14

0

Temperature is
displayed in °F

1

Temperature is displayed in
°C

Clock format

16

0

12-hour clock format

1

24-hour clock format

Intelligent Fan™
operation

17

2

Fan operates
continuously in
Occupied and
Recovery mode. Fan
operates with call for
heating or cooling in
Unoccupied mode.

0 or 1

0—Fan only operates with

calls for heating or cooling
in Occupied and
Unoccupied modes.

1—Fan operates

continuously in Occupied
mode. Fan operates with
calls for heating or cooling
in Unoccupied mode.

Auxiliary Contact
Operation

18

0

0—Time of day

contacts

1

1—Economizer contacts

Fan key
adjustment
(models with Fan
key only)

21

0

Fan setting key is
operational

1

Fan setting key is Auto only

Remote sensing 22

0

Remote sensing not
activated

1

Remote sensing activated

Keypad lockout
level (keypad
lockout is
enabled and
disabled by DIP
switch 1 on back
of thermostat)

25

0

No lockout

1 or 2, 3

1—Lockout all keys on

thermostat except system
and fan settings, temporary
setpoint, clock and day
adjustments

2—Lockout all keys except

Set Current Day/Time,
increase

and decrease

keys.

3—Lockout all keys except

Temporary Occupied, Set
Day and Clock keys

Duration of
temporary
override

26

3

3—Three hour

override

1, 8 or 12 1—One hour override

8—Eight hour override
12—Twelve hour override

Minimum off time
for the
compressor

33

4

4 minute minimum off
time for the
compressor

0, 1, 2, 3
or 5

Minimum number of minutes
(0 thru 5) the compressor will
be off between calls for the
compressor