T7300D SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTAT

Table 4. Installer System Test Options.

Heat

Auto

System

Fan

Off

Auto

Un

Mon

Wait

Lo

In

Room

Remote

%Humid

Auto

Sav

AM

PM

Comm

Cool

Duct

Only

On

Recovery

Hi

Med

Cool

TueWedThuFriSatSun

Occupied 12 Override

M4916

Aux Ht

Em Ht

Em Ht

Set Program

Set Program

Set Day/Time

Set Day/Time

Start Time

Temporary Setting Enrg

Em Heat

M10257A

TEST NUMBER

4.. Press Run Program.

INSTALLER SYSTEM TEST

Use the Installer System Test to check the thermostat
configurations and operation. Refer to Table 3 for a list of
the available system tests.

Table 3. Tests Available in Installer System Test.

Fig. 6. Display of test number.

Refer to Table 4 and Thermostat Information section for
directions and results of the specific system tests.

NOTE:

Press Run Program to exit the system test. The
system test times out after four minutes without
any key presses.

M4954A

Set Program

Set Temperature

Change

Time/Temp

Occupied

Temp

Unoccupied

Start Time

Day

System

Fan

Copy

Occupied
Start Time

Run

Program

Temporary

Occupied

Continous

Unoccupied

Set Current

Day/Time

Clear

Start Time

Unoccupied

Temp

Heat/Cool

Settings

Auto

System

Fan

Mon

Room

AM

Occupied 1

Heat

Run

Program

To start the system test:

CAUTION

The minimum off time for compressors is bypassed
during the Installer System Test. Equipment
damage can occur if the compressor is cycled too
quickly.

Press and hold the increase

and

decrease keys, at

the same time, until 10 appears. All segments of the LCD
are displayed for three seconds before 10 appears. See
Fig. 5 and 6.

Fig. 5. Display of all the segments of the LCD.

(continued)

Key to

Press

Test

Number

Description

Heating Equipment System Test

Heat/Cool Settings

10

Enter heating equipment system test.

11

Stage-one heat comes on. When Installer Setup number 02 is 01, the system fan
is also energized.

12

Stage-two heat comes on. Stage-one heat and system fan remain on.

13

Stage-three heat comes on. Stage-one and stage-two heat with the system fan
are on.

12

Stage-three heat turns off.

11

Stage-two heat turns off.

10

Stage-one heat and system fan turn off.

Test

Number

System Test Description

10 to 19

Heating equipment can be turned on and off

30 to 39

Cooling equipment can be turned on and off

40 to 49

Fan equipment can be turned on and off

60 0 to
60 19

Keyboard keys test

70 to 79

Thermostat information including date code,
software versions and subbase identification
are displayed