Thermostat information – Honeywell SERIES 2000 T7300D User Manual

Page 7

Advertising
background image

62-0132

7

T7300D SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTAT

Thermostat Information

1. Press the Heat/Cool Settings key to access the

thermostat information.

M4934

2. Press the increase

key to display the production

date code. The first two large digits are the month
and the third digit is the last digit of the year.
(Example: 036 = March 1996)

M4931

3. Press the increase

key again to display the

software identification code. (Example: 02 =
software ID code 2)

M4932A

4. Press the increase

key again to display the

software revision number. (Example: 001 = revision
number 1)

M10229

Table 4. Installer Self-Test Options (Continued).

Key to

Press

Test

Number

Description

Cooling Equipment System Test

Heat/Cool Settings

30

Change from heating to cooling equipment system test.

31

Stage-one cooling and system fan come on.

32

Stage-two cool comes on. Stage-one cool and system fan remain on.

33

Stage-three cool comes on (Q7300G only). Stage-one and stage-two cool with
system fan remain on.

32

Stage-three cool turns off.

31

Stage-two cool turns off.

30

Stage-one cool and system fan turn off.

Fan Equipment System Test

Heat/Cool Settings

40

Change from cooling to fan equipment system test.

41

Fan comes on.

40

Fan turns off.

Key Operation System Test

Heat/Cool Settings

60 2

Change from fan to key operation system test.

Unoccupied Temp

60 0

Unoccupied Temp test number is displayed.

Occupied Temp

60 1

Occupied Temp test number is displayed.

60 3

Increase test number is displayed.

60 5

Decrease test number is displayed.

Clear Start Time

60 7

Clear Start Time test number is displayed.

Day

60 8

Day test number is displayed.

Copy

60 9

Copy test number is displayed.

Unoccupied Start

TIme

60 10

Unoccupied Start Time test number is displayed.

System

60 11

System test number is displayed.

Fan

60 12

Fan test number is displayed.

Set Current

Day/Time

60 14

Set Current Day/Time test number is displayed.

Run Program

60 15

Run Program test number is displayed.

Temporary

Occupied

60 16

Temporary Occupied test number is displayed.

Occupied Start Time

60 17

Occupied Start Time test number is displayed.

Continuous

Unoccupied

60 19

Continuous Unoccupied test number is displayed.