Hobart Welding Products STELLAR AT OM-2208 User Manual

Page 16

Advertising
background image

OM-2208 Page 12

3-2. Weld Output Receptacles And Selecting Cable Sizes

Y

ARC WELDING can cause Electromagnetic Interference.

To reduce possible interference, keep weld cables as short as possible, close together, and down low, such as on the floor.
Locate welding operation 100 meters from any sensitive electronic equipment. Be sure this welding machine is installed
and grounded according to this manual. If interference still occurs, the user must take extra measures such as moving
the welding machine, using shielded cables, using line filters, or shielding the work area.

Weld Cable Size** and Total Cable (Copper) Length in Weld Circuit

Not Exceeding***

100 ft (30 m) or Less

150 ft

(45 m)

200 ft

(60 m)

250 ft

(70 m)

300 ft

(90 m)

350 ft

(105 m)

400 ft

(120 m)

Weld Output

Terminals

Y

Turn off power before
connecting to weld out-
put terminals.

Y

Do not use worn, dam-
aged, undersized, or
poorly spliced cables.

Welding

Amperes

10 – 60%

Duty

Cycle

60 – 100%

Duty

Cycle

10 – 100% Duty Cycle

100

4 (20)

4 (20)

4 (20)

3 (30)

2 (35)

1 (50)

1/0 (60)

1/0 (60)

150

3 (30)

3 (30)

2 (35)

1 (50)

1/0 (60)

2/0 (70)

3/0 (95)

3/0 (95)

200

3 (30)

2 (35)

1 (50)

1/0 (60)

2/0 (70)

3/0 (95)

4/0 (120)

4/0 (120)

250

2 (35)

1 (50)

1/0 (60)

2/0 (70)

3/0 (95)

4/0 (120)

2 ea. 2/0

(2x70)

2 ea. 2/0

(2x70)

300

1 (50)

1/0 (60)

2/0 (70)

3/0 (95)

4/0 (120)

2 ea. 2/0

(2x70)

2 ea. 3/0

(2x95)

2 ea. 3/0

(2x95)

350

1/0 (60)

2/0 (70)

3/0 (95)

4/0 (120)

2 ea. 2/0

(2x70)

2 ea. 3/0

(2x95)

2 ea. 3/0

(2x95)

2 ea. 4/0

(2x120)

+

400

1/0 (60)

2/0 (70)

3/0 (95)

4/0 (120)

2 ea. 2/0

(2x70)

2 ea. 3/0

(2x95)

2 ea. 4/0

(2x120)

2 ea. 4/0

(2x120)

Output Receptacles

500

2/0 (70)

3/0 (95)

4/0 (120)

2 ea. 2/0

(2x70)

2 ea. 3/0

(2x95)

2 ea. 4/0

(2x120)

3 ea. 3/0

(3x95)

3 ea. 3/0

(3x95)

600

3/0 (95)

4/0 (120)

2 ea. 2/0

(2x70)

2 ea. 3/0

(2x95)

2 ea. 4/0

(2x120)

3 ea. 3/0

(3x95)

3 ea. 4/0

(3x120)

3 ea. 4/0

(3x120)

*

This chart is a general guideline and may not suit all applications. If cable overheating occurs (normally you can smell it), use next size larger

cable.

**Weld cable size (AWG) is based on either a 4 volts or less drop or a current density of at least 300 circular mils per ampere.
( ) = mm

2

for metric use

S-0007-E–

***For distances longer than those shown in this guide, call a factory applications representative at 920-735-4505.

Advertising