Caution, 5. electrical service guide – Hobart Welding Products STELLAR AT OM-2208 User Manual

Page 18

Advertising
background image

OM-2208 Page 14

3-5. Electrical Service Guide

Y

CAUTION:

INCORRECT INPUT POWER can damage this welding power source. This welding pow-

er source requires a CONTINUOUS supply of 60 Hz (

+

10%) power at

+

10% of rated input voltage. Do

not use a generator with automatic idle device (that idles engine when no load is sensed) to supply
input power to this welding power source.

Actual input voltage should not exceed

±

10% of indicated required input voltage. If

actual input voltage is outside of this range, output may not be available.

NOTE

60 Hz Three Phase

60 Hz Single

Phase

Input Voltage

230

460

575

230

460

Input Amperes At Rated Output

31

15

12

53

27

Max Recommended Standard Fuse Rating In Amperes

1

Time-Delay

2

35

15

15

60

30

Normal Operating 3

45

20

20

80

40

Min Input Conductor Size In AWG/Kcmil

10

14

14

8

10

Max Recommended Input Conductor Length In Feet (Meters)

112

(34)

175

(53)

274

(83)

85

(26)

224

(68)

Min Grounding Conductor Size In AWG/Kcmil

10

14

14

8

10

Reference: 1999 National Electrical Code (NEC)

1 Consult factory for circuit breaker applications.

2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and

above).