Vent information and diagrams, B. vent system confi guration, A. vent guidelines – Hearth and Home Technologies GBST4336I User Manual

Page 23

Advertising
background image

23

Heatilator • GBST4336I, GBFL4136I • 2135-900 Rev. D • 11/08

7

7

Vent Information and Diagrams

B. Vent System Confi guration

CAUTION! Risk of Fire! ALL vent confi guration specifi -
cations MUST be followed.

This product is tested and listed

to these specifi cations. Appliance performance will suffer if
specifi cations are not followed.

Rise to Run Ratio = 2:1

Maximum Total Horizontal Run = 15 ft.

Minimum Total Vertical Rise for 0-2 Elbows = 12 ft.

Maximum Total Vertical Rise = 50 ft.

Maximum Number of Elbows: Four 90º or six 45º

Minimum Total Vertical Rise for Four 90º or six 45º
Elbows=16 ft.

See Figures 7.1, 7.2, 7.3.

Figure 7.1 Minimum Total Vertical Rise

A. Vent Guidelines

WARNING!

Fire Risk/Asphyxiation! This appliance requires

the specifi ed pipe for operation. Incorrect pipe may cause spill-
age, condensation and overheating.

Figure 7.2 Rise to Run Ratio

These models require the following size B-Vent double
wall.

METAL

PLUMBERS' STRAP

MAXIMUM HORIZONTAL RUN IS 50%

OF VERTICAL. HORIZONTAL RUN

CANNOT BE MORE THAN 15 FT.

VENT SUPPORTS

ARE PER VENT

MANUFACTURER'S

SPECIFICATIONS.

METAL

PLUMBER’S

STRAP

12 FEET
MINIMUM
50 FEET
MAXIMUM

VENT SUPPORTS ARE PER

VENT MANUFACTURER’S

SPECIFICATIONS

MINIMUM CLEARANCES

ARE PER VENT

MANUFACTURER’S

SPECIFICATIONS

• Follow pipe manufacturer’s installation guidelines when

installing the appliance.

WARNING!

Fire Risk/Explosion/Asphyxiation!

DO NOT

connect this gas appliance to a chimney fl ue serving a
separate solid-fuel or gas burning appliance.

• Vent this appliance directly outside.

• Use separate vent system for this appliance.

May impair safe operation of this appliance or other appli-
ances connected to the fl ue.

WARNING! Risk of Fire or Explosion!

Insulation and oth-

er combustibles must not infringe on clearances.

• ALWAYS maintain specifi ed clearances around venting and

fi restop systems.

• Install fi restops as specifi ed.

Failure to keep insulation or other material away from vent pipe
may cause fi re.

Figure 7.3 Proper Use of Elbows

45 DEGREES

ELBOW

90 DEGREES

ELBOW

OFFSETS EXCEEDING

45 DEGREES ADAPT

HORIZONTAL LIMITATIONS

MAXIMUM

HORIZONTAL

15 FEET

MINIMUM

VERTICAL

9 FEET

Note: Maximum horizontal
distance is 50% vertical vent
height.

Models

Pipe Size

GBST4336I

5 inches

GBFL4136I

5 inches