27

ROOM ABOVE (non-insulated ceiling)

ATTIC ABOVE (insulated ceiling)

B

A

Ceilng firestop from

bottom

Ceiling firestop from

top

Note:

Use same dimensional lumber for framing

ceiling firestop and joists.

Figure 8.5 Installing the Ceiling Firestop

• Install a ceiling fi restop whenever chimney penetrates

ceiling/fl oor.

• Mark and cut an opening in ceiling as shown in

Figure 8.5.

• Frame the opening with the same size lumber used in the

ceiling joists.

• Nail the ceiling fi restop to the bottom of the ceiling joists

when there is a room above/

• Use an attic insulation shield if the ceiling is insulated. The

ceiling fi restop may then be attached above or below the
joists. Refer to Figure 8.6 and 8.7.

D. Install Ceiling Firestops

CAUTION! Risk of Fire! Ceiling fi restops must be used
whenever the chimney penetrates a ceiling/fl oor.
• Chase construction requires ceiling fi restops at each fl oor

or every 10 ft (3.05 m) of clear space.

• The

ceiling

fi restop slows spread of fi re and reduces cold

air infi ltration.

WARNING! Risk of Fire! DO NOT seal area between

fi restop opening and chimney pipe except where they
enter the attic or leave the warm-air envelope of the
home (use 600° F sealant).

Heatilator • Birmingham BIR42 • 4059-308 Rev E • 08/08

Catalog #

A

B

in.

mm

in.

mm

FS538

17

432

17

432

FS540

17

432

26

660