Troubleshooting Tips

The table below lists typical symptoms and the corresponding solution(s).

Symptom/condition

Probable Cause

Solution

The motor

will not run.

The inverter

outputs U, V, W

are not supply-

ing voltage.

•

Is the frequency command source
A01 parameter setting correct?

•

Is the Run command source A02
parameter setting correct?

•

Make sure the parameter
setting A01 is correct.

•

Make sure the parameter
setting A02 is correct.

•

Is power being supplied to termi-
nals L1, L2, and L3(N)? If so, the
POWER lamp should be on.

•

Check terminals L1, L2, and
L3(N), then U/T1, V/T2,
and W/T3.

•

Turn on the power supply or
check fuses.

•

Is there an error code

EXX

displayed?

•

Press the Func. key and
determine the error type.
Then clear the error (Reset).

•

Are the signals to the intelligent
input terminals correct?

•

Is the Run Command active?

•

Is the [FW] terminal (or [RV])
connected to P24 (via switch, etc.)

•

Verify the terminal functions
for C01 - C05 are correct.

•

Turn on Run Command.

•

Supply 24V to [FW] or [RV]
terminal, if configured.

•

Has the frequency setting for F01
been set greater than zero?

•

Are the control circuit terminals H,
O, and L connected to the potenti-
ometer?

•

Set the parameter for F01 to
a safe, non-zero value.

•

If the potentiometer is the
frequency setting source,
verify voltage at “O” > 0V.

•

Is the RS (reset) function or FRS
(free-run stop) function on?

•

Turn off the command(s).

Inverter outputs
U, V, W are
supplying
voltage.

•

Is the motor load too heavy?

•

Reduce load, and test the
motor independently.

The optional
remote operator
is used (DR/W)

•

Are the operational settings
between the remote operator and
the inverter unit correct?

•

Check switches 1 and 2 on
the optional remote operator
(copy unit).

The direction of the motor is

reversed.

•

Are the connections of output
terminals U/T1, V/T2, and W/T3
correct?

•

Is the phase sequence of the motor
forward or reverse with respect to
U/T1,V/T2, and W/T3?

•

Make connections according
to the phase sequence of the
motor. In general:
FWD = U-V-W, and
REV=U-W-V.

•

Are the control terminals [FW] and
[RV] wired correctly?

•

Is parameter F04 properly set?

•

Use terminal [FW] for
forward, and [RV] is reverse.

•

Set motor direction in F04.

2

1

4

3

ON

OFF

1: Off

2: On