Output Function Adjustment Parameters

The overload level parameter (C41)sets the
motor current level at which the overload
signal becomes true. The range of settings
is from 0% to 200% of the rated current
for the inverter. This function is for gener-
ating an early warning logic output,
without causing either a trip event or a
restriction of the motor current (those
effects are available on other functions).

The frequency arrival signal is intended to
indicate when the inverter output has
reached (arrived at) the target frequency.
You can adjust the timing of the leading
and trailing edges of the signal via two
parameters specific to acceleration and
deceleration ramps, C42 and C43.

The Error for the PID loop is the magni-
tude (absolute value) of the difference
between the Setpoint (desired value) and
Process Variable (actual value). The PID
output deviation signal (output terminal
function option code 04) indicates when
the error magnitude has exceeded a magni-
tude you define.

0

Motor

current

C41

time

Overload

signal

1

0

Output

frequency

C42

time

Arrival

signal

C43

1

0

PID Error

(PV-SP)

C44

time

Deviation

Signal

1

SP

“C” Function

Run-

time
Edit

Defaults

DOP,DRW,DOP+

Func.

Code

Name

Description

EU/

US

Units

Func.

Code

Name

C41

Overload level setting Sets the overload signal level

between 0% and 200% (from 0
to two times the rated current
of the inverter)

(rated current

for each

inverter)

F-33

OV Load

C42

Frequency arrival
setting for accel.

Sets the frequency arrival
setting threshold for the output
frequency during acceleration

0.0

Hz

F-32

ARV ACC

C43

Arrival frequency
setting for decel.

Sets the frequency arrival
setting threshold for the output
frequency during deceleration

0.0

Hz

F-32

ARV DEC

C44

PID deviation level
setting

Sets the allowable PID loop
error magnitude (absolute
value), SP - PV, range is 0.0 to
100%, resolution is 0.1%

3.0

%

F-33

OV PID