Troubleshooting

T

roub

le

shoot

in

g

and Maint

enance

6–4

The motor speed will not reach

the target frequency (desired

speed).

•

If using the analog input, is the
current or voltage at “O” or “OI?”

•

Check the wiring.

•

Check the potentiometer or
signal generating device.

•

Is the load too heavy?

•

Reduce the load.

•

Heavy loads activate the
overload restriction feature
(reduces output as needed).

The rotation is unstable.

•

Is the load fluctuation too great?

•

Is the supply voltage unstable?

•

Is the problem occurring at a partic-
ular frequency?

•

Increase the motor capacity
(both inverter and motor).

•

Fix power supply problem.

•

Change the output frequency
slightly, or use the jump
frequency setting to skip the
problem frequency.

The RPM of the motor does not
match the inverter output
frequency setting.

•

Is the maximum frequency setting
A04 correct?

•

Does the monitor function D01
display the expected output
frequency?

•

Verify the V/F settings
match motor specifications.

•

Make sure all scaling (such
as A11 to A14) is properly
set.

Inverter data

is not

correct.

No downloads

have occurred.

•

Was power turned off after a
parameter edit but before pressing
the Store key?

•

Edit the data and press the
Store key once.

•

Edits to data are permanently
stored at power down. Was the time
from power Off to power On less
than six seconds?

•

Wait six seconds or more
before turning power Off
after editing data.

A download to
the inverter was
attempted.

•

Was the power turned off within six
seconds after the display changed
from REMT to INV?

•

Copy the data to the inverter
again, and keep power on for
six seconds or more after
copying.

A parameter

will not

change after

an edit

(reverts to

old setting).

True for certain
parameters

•

Is the inverter in Run Mode? Some
parameters cannot be edited during
Run Mode.

•

Put inverter in Stop Mode
(press the Stop/reset key).
Then edit the parameter.

True for all
parameters

•

If you’re using the [SFT] intelligent
input (software lock function), — is
the [SFT] input on?

•

Is switch 4 (located on the back of
the remote operator copy unit) On?

•

Change the state of the SFT
input, and check the B31
parameter (SFT mode).

•

Turn the switch off.

Symptom/condition

Probable Cause

Solution