69-0348—1

mask no. and

System

Press

Look for this

Switch

This

Response

Position

Key

Key Down

Key Released

OFF

03

Blank

07

Blank

15

Blank

COOL or

15

Cooling, fan and

15

Cooling, fan and

OFF

06

Blank

02

Blank

05

Blank

04

Blank

01

Blank

00

Blank

12

See note A

OFF

08

Blank

13

Microprocessor

09

Blank

14

Blank

HEAT or

14

14

14

14

OFF

10

Blank

11

END SELF-TEST

A HEAT displayed when system switch is in HEAT, COOL

when in COOL, HEAT or COOL when in AUTO, neither
when in OFF. Also, a four-digit code is displayed, with each
digit explained on the next page.

AUTO (with
fan in AUTO)

CHANGE

TO LAST

PERIOD

SKIP

NEXT

PERIOD

PRESENT

SETTING

PRESENT

SETTING

PRESENT

SETTING

WARMER

COOLER

AHEAD

BACK

LEAVE

RETURN

WAKE

SLEEP

DAY

SET

HEAT/COOL

SET

PRESENT
DAY/TIME

SYSTEM LED on.

SYSTEM LED off.

revision no.

1st stage heating,
fan and SYSTEM
LED on.

AUTO
(with fan
in AUTO)

2nd stage heating
and AUX. HEAT
LED also on.
2nd stage heating
and AUX. HEAT
LED off.

1st stage heating,
fan and SYSTEM
LED off.

Normal operating
display.

SET

PRESENT
DAY/TIME

SET

PRESENT
DAY/TIME

HOLD
TEMP

SET

PRESENT
DAY/TIME

SET

PRESENT
DAY/TIME

RUN

PROGRAM

(CHECK
EACH
POSITION)

Perform the following test as a check of all thermostat

functions. If thermostat does not respond as indicated, ther-
mostat must be replaced.

1. Press AHEAD and BACK keys at the same time.

While holding keys down, all segments of the display should
be on, see Fig. 10.

2. Set system switch to OFF. Press AHEAD and BACK

and PRESENT SETTING keys at the same time to enter
self-test.

Fig. 10—All segments on display.

M410C

SUN MON TUE WED THU FRI SAT COOL

ON HEAT ON

WAKE LEAVE RETURN SLEEP

TEMPORARY

REPL

BAT

AM
PM

SET
PT

3. Press each key as listed below, and look for response

listed, as key is held down and released.