Heat & Glo LifeStyle Collection • Twilight-II-B • 2108-900 Rev. M • 11/08

Apply housewrap or building paper

For placement of combustible housewrap or building pa-
per and non-combustible sheathing for the outside wall
see Figures 7.5 and 7.6.

Special care should be taken when choosing building
materials for weather proofi ng (i.e. building wraps, seal-
ant tapes, liquid sealants, rubberized fl ashings, etc.).
All sealant materials or building wraps installed within 6
inches of the top and sides of the fi replace surround must
be approved to a minimum temperature of 225º F con-
tinuous exposure. Consult the material’s manufacturer to
ensure product compliance.

Figure 7.6

METAL FLASHING

TOP OF SURROUND

EDGE OF SURROUND

6 IN.

6 IN.

Figure 7.5 Outside View without Non-combustible Sheathing Shown

* NOTE: All fi nishing materials on top of exterior sheathing

must be non-combustible for a minimum of 12 inches
above and on both sides of the exterior face of the
appliance. This non-combustible fi nishing material can
be up to a maximum of 6 inches thick (6 inches maximum
horizontal overhang) to allow for brick and stone alcoves
(see Figure 8.5).

** NOTE: Combustible house wrap or building paper

MUST NOT extend over the outside of non-combustible
sheathing, and MAY extend over the fl ashing behind non-
combustible sheathing. Use high temp silicone or sealant
recommended by the manufacturer of the housewrap to
seal between combustible sheathing house wrap and non-
combustible sheathing. The sealant material used within
6 inches of the top and sides of the fi replace surround
must be approved to a minimum temperature of 225º F
continuous exposure.

Figure 7.7 Non-combustible Zone (Exterior)

Risk of Fire

• Non-combustible clearances must be main-

tained.

• Sheetrock, wood or other combustibles must

NOT be used as sheathing or facing in the non-
combustible zone.

• See Sections 3 and 8 for proper clearances.

• See Section 1 for combustible /non-combus-

tible defi nitions.

Once the appliance is in place use enough high tempera-
ture silicone sealant or manufacturer specifi ed sealant
(approved to a minimum of 225º F) to make a water tight
seal between outdoor surround and exterior sheathing.

Face the perimeter of the appliance with non-combustible
sheathing over shroud fl anges and fl ashing. See Figure
7.7 for non-combustible zone.

WARNING

APPLIANCE

TL-TRIM KIT

HOOD

TOP HOOD

TOP OF

FIREPLACE

16-5/16 in.

WALL STUD

HOUSEWRAP

INSULATION

HOUSEWRAP

**

(BUILDING
PAPER) OVERLAP
FLASHING 1 in.

SHEATHING,

COMBUSTIBLE

FIREPLACE

HEADER

INSULATED

FRAMING

STANDOFF

NON-COMBUSTIBLE

*

SHEATHING

12 in.

FLASHING

HEADER

2-3/4 in.

2-3/4 in.

12 in.

= NON-COMBUSTIBLE ZONE