Finishing, A. mantel and wall projections, B. facing material – Hearth and Home Technologies Indoor/Outdoor Gas Fireplace Twilight-II-B User Manual

Page 30

Advertising
background image

Heat & Glo LifeStyle Collection • Twilight-II-B • 2108-900 Rev. M • 11/08

30

A. Mantel and Wall Projections

WARNING! Risk of Fire! Comply with all minimum clear-
ances as specifi ed. Framing closer than the minimums list-
ed must be constructed entirely of noncombustible materi-
als (i.e., steel studs, concrete board, etc.) Failure to comply
could cause fi re.

B. Facing Material

Inside Facing Material

• May install combustible materials up to specified

clearances on top, front and sides of appliance.

• Seal joints between fi nished wall and appliance top and

sides with 300º F (140º C) minimum sealant.

• Leave space so bottom grille can be lowered for trim

door removal.

WARNING! Risk of Fire! DO NOT apply combustible
materials beyond the minimum clearances. Comply with
all minimum clearances to combustibles as specifi ed in
this manual. Overlapping materials could ignite and will
interfere with proper operation of doors and louvers.

10

10

Finishing

12

11

10

9

8

7

6

13-5/8

12-5/8

11-5/8

10-5/8

9-5/8

8-5/8

7-5/8

HOOD

NON-COMBUSTIBLE BOARD

(SUPPLIED ON APPLIANCE)

INDOOR SIDE ONLY

CEILING

35-3/4

MEASURED

FROM CORNER

TOP VIEW

FIREPLACE

HOOD

1/2 IN.

Note: Measurements are in inches.

41-7/8 in.

2-3/4 in.

NON-COMBUSTIBLE ZONE

Figure 10.3 Non-combustible Zone (Interior)

Outside Facing Material

Figure 10.4 Exterior View - Minimum Clearances

Vinyl

Non-vinyl

A

36 in.

12 in.

B

64-5/16 in.

35-5/16 in.

OVERHANG

A

A

B

SIDING

SIDING

SIDING

FINISHING MATERIALS

A

Figure 10.1 Clearances to a Combustible and/or Non-combustible

Indoor Mantel

Figure 10.2 Clearances to a Combustible and/or Non-combustible

Indoor Mantel or Mantel Leg