Installing the fireplace, Step 1 locating the fireplace – Hearth and Home Technologies 6000TRS-CE User Manual

Page 10

Advertising
background image

10

A

B

C

D

E

106.6cm

55.9cm

100.3cm

143.5cm

203.2cm

*

Figure 2. Fireplace Dimensions, Locations, and

Space Requirements

1”MIN. (2.54cmm)

A

B

D

E

20”

(50.8cm)

C

3

Installing the
Fireplace

The diagram below shows space and clearance
requirements for locating a fireplace within a room.

Step 1
Locating the
Fireplace

NOTE:
Dimensions are
shown with the
sides, back
and/or corners
of the unit
touching the wall.

Clearance Requirements

The top and back of the fireplace are defined by
stand-offs.

The minimum clearance to a perpendicular wall
extending past the face of the fireplace is 7.62cm.

The back of the fireplaces may be recessed into
combustible construction (see Figure 3).

MODEL: 6000TRS-CE RECESSED DEPTH: 54.6cm

Minimum Clearances from the Fireplace to Combustible Materials

Glass
Front

Floor

Back of

Fireplace

Sides of

Fireplace

Top of

Fireplace

Ceiling

91.4cm

0

1.3cm

1.3cm

8.9cm

79cm

Figure 3. Minimum Clearances

Minimum Clearances from the Flue Pipe to Combustible Materials

For Horizontal Sections

For Vertical

Sections

At Wall Firestops

Top

Bottom

Sides

Top

Bottom

Sides

7.6cm

2.54 cm

2.54 cm

2.54 cm

6.4 cm

1.3 cm

2.54 cm