FIGURE 18. Flue Pipe & Firestop

For Vertical Runs - One firestop is REQUIRED at the
hole in each ceiling through which the flue passes.

To install firestops for vertical runs that pass through
ceilings:

• Position a plumb bob directly over the center of the ver-

tical flue component.

• Mark the ceiling to establish the centerpoint of the flue.

• Drill a hole or drive a nail through this center point.

• Check the floor above for any obstructions, such as

wiring or plumbing runs.

• Reposition the heater and flue system, if necessary, to

accommodate the ceiling joists and/or obstructions.

• Cut a 25.4cm X 30.5cm hole through the ceiling, using

the firestop pipe opening as a guide.

• Frame the hole with framing lumber the same size as

the ceiling joists.

FIGURE 19. Hole and New Framing Members

CEILING

NEW
FRAMING
MEMBERS

EXISTING CEILING
JOISTS

CHIMNEY
HOLE

10" (25.4 cm)

10” (25.4 cm)

10" (25.4 cm)

12" (30.5 cm)

INTERIOR

WALL SHIELD