Hearth and Home Technologies Hudson Bay Direct Vent Gas Appliance HUDBAY-FS User Manual

Page 13

Advertising
background image

10/08

Page 13

Quadra-Fire • Hudson Bay • 7003-121 Rev. i

NOTE:
(1) Installation requires a minimum of 6 in. (152mm)

horizontal run of vent with a 1/4 in. (6mm) rise run towards
the termination. Each 1 ft. (305mm) of horizontal venting
must include a 1/4 in. (6mm) rise. Never allow the vent
to run downward. This could cause high temperatures
and may present the possibility of a house or structure
fire.

(2) The location of the horizontal vent termination on an

exterior wall must meet all local and national building
codes, and must not be easily blocked or obstructed,
see

Figure 4.4 on page 8.

(3) For installations requiring a vertical rise on the exterior

of the building, the HHT RHVK snorkel kit (Part #844-
8921) is available with a 14 in. (356mm) and a 36 in.
(914mm) tall snorkel termination cap. Follow the
same installation procedures as used for standard
horizontal terminations. If the snorkel termination must
be installed below grade (i.e. basement application),
proper drainage must be provided to prevent water from
entering the snorkel termination. Do not backfill around
snorkel termination.

HOT

HOT

WOOD
SCREW

WALL THIMBLE

PART HHW2 PART
841-0670 (Preferred)

Step 4.
Position the horizontal termination cap in the center of the 10
in. x 10 in. (254mm x 254mm) square hole and run a bead
of non-hardening mastic around its outside edges, so as to
make a seal between it and the wall, attach termination cap
to the exterior wall with the four wood screws provided. The
arrow on the vent cap should be pointing up (

Figure 5.6).

Figure 5.6

8 in.

(203mm)

7 in.

(178mm)

7 in.

(178mm)

6 in.

(152mm)

Figure 5.7

NOTES:
(1) The four wood screws provided should be replaced with

appropriate fasteners for stucco, brick, concrete, or
other types of sidings.

(2) Termination cap HHW2 (Part #841-0670) is highly

recommended on a building with vinyl siding, as the
vinyl siding standoff is built in. The pilot hole will be 2 in.
(51mm) closer to the bottom of the square than the top.
Using a framing square, draw a 14 in. x 14 in. (356mm x
356mm) square around the pilot hole in the siding. See

Figure 5.7.

(

NOTE: If you are installing termination cap HHW2, the

pipe will be off center on the flashing). Ensure that proper
clearances to combustible materials are maintained.

If

you are using an approved termination cap other than
HHW2 on a building with vinyl siding, a vinyl siding
standoff should be installed between the vent cap and
the exterior wall (

Figure 5.8, on the next page). Attach

the vinyl siding standoff to the horizontal termination
cap. The vinyl siding standoff prevents excessive heat
from possibly melting the vinyl siding material. The vent
termination cap shall not be recessed into a wall or
siding. Remove siding from the area where the standoff
will be located.

Figure 5.5

CENTER
LINE

CENTER
LINE

CENTER OF
HOLE

WALL
THIMBLE

Advertising