Hearth and Home Technologies CFX-Crescent User Manual

Page 19

Advertising
background image

Heat & Glo • CFX-CRESCENT • 705-900 Rev. P • 12/07

19

For Vertical Runs - The vent system must be
supported every eight (8) feet (2.4 m) above the
fireplace flue outlet by wall brackets.

To install support brackets for vertical runs:

• Attach wall brackets to the vent pipe and secure

the wall bracket to the framing members with
nails or screws.

Use wall brackets to
support vertical runs
every 8 feet (2.4 m)
above the fireplace flue
outlet.

Figure 11. Installing Support Brackets

4. Install Firestops

For Horizontal Runs - Firestops are REQUIRED
on both sides of a combustible wall through which
the vent passes. The exterior firestop is not required
at the termination cap for model CFX-Crescent. (SLK-
01TRD is required for horizontal terminations).

To install firestops for horizontal runs that pass
through either interior or exterior walls:

• Cut a 10-inch by 10-inch (254 mm X 254 mm)

hole through the wall. The center of the hole is
one (1) inch (25.4 mm) above the center of the
horizontal vent pipe.

WALL BRACKET

WALL STUD

8 FT.

(2.3m)

FLUE

OUTLET

1 INCH MIN.

(25.4m)