SECTION 6 – OPERATING AUXILIARY EQUIPMENT

6-1.

Auxiliary Power Receptacles And Circuit Breakers

Y

If unit does not have GFCI recep-
tacles, use GFCI-protected exten-
sion cord.

.

Auxiliary power decreases as weld
current increases.

1

240 V 50 A AC Receptacle RC3

RC3 supplies 60 Hz single-phase power at
weld/power speed. Maximum output is 12
kVA/kW.

2

120 V 15 A AC Duplex Receptacle
RC2

3

120 V 15 A AC Duplex Receptacle
RC1

RC2 and RC1 supply 60 Hz single-phase
power at weld/power speed. Maximum out-

put from RC2 or RC3 is 1.8 kVA/kW.

4

240 V 30 A, AC Twistlock Receptacle
RC6

RC6 supplies 60 Hz three-phase power at
weld/power speed. Maximum output is 12
kVA/kW.

5

Circuit Breaker CB3

CB3 protects RC1, RC2, and RC3 from
overload. If CB3 opens, RC1, RC2, and
RC3 do not work. Place switch in On posi-
tion to reset breaker.

6

Circuit Breakers CB1 And CB2

CB1 protects RC1 and CB2 protects RC2
from from overload. If CB1 or CB2 opens,

the receptacle does not work. Press button
to reset breaker.

7

Circuit Breaker CB13

CB13 protects RC6 from overload. If CB13
opens, the receptacle does not work. Push
breaker bar up to reset.

.

If a breaker continues to open, contact
Factory Authorized Service Agent.

Combined output of all receptacles limited
to 12 kVA/kW rating of the generator.

EXAMPLE: If 13 A is drawn from RC1 and
RC2, only 37 A is available at RC3:

2 x (120 V x 13 A) + (240 V x 28 A) = 12
kVA/kW

8

Auxiliary Power While Welding Table

1

2

3

7

6

4

200 379 / 189 438-B

SIMULTANEOUS WELDING AND AUXILIARY POWER

Three-Phase

240 V

Receptacle

Amperes

Single-Phase

240 V

Receptacle

Amperes

Total

Power

In Watts

Weld

Current

In Amperes

120 V

Receptacle

Amperes

350
300
250
200
150
100

50

0

11900

9600
7500
5600
3900
2400
1100

0

16
38
40
40
40
40
40


5

15
30
35
40
45
50


4

10
13
19
23
26
30

8

5