These surfaces

must be covered

with non-combustible

material.

Non-combustible

sealant.

D. Finishing Material

Refer to Sections 12.A. and Sections 12.B. for combustible/

non-combustible materials. Refer to Figure 12.10 for non-

combustible zone.

WARNING! Risk of Fire! You must maintain clearances.

• Use only non-combustible framing material below

standoffs.

• Sheetrock, wood or other combustibles must NOT be used

as sheathing or facing in the non-combustible zone.

• DO NOT cover metal fireplace front with combustible

materials.

• Install combustible materials only to specified clearances

on top front and side edges.

• Complete framing and apply facing material (drywall) over

framing.

• A bead of 300-deg F minimum non-combustible sealant

must be used to close off any gaps at the top and sides

between the fireplace and facing to prevent cold air

leaks.

• Large gaps can be bridged with fiberglass rope gasket.

• Only non-combustible materials may be used to cover the

metal fireplace front.

Figure 12.9 Non-combustible Facing

Metal strips are placed 2 in. (51 mm)

under the front of the fireplace and must

extend beyond the front and sides of

fireplace opening by 2 in. (51 mm)

Continuous,

non-combustible sealant

Floor constructed of wood or

other combustible material

1 in. Micore

or equivilent

insulation &

1/2 in. Durock

Bottom of fireplace opening

and finished hearth may be

the same height

Finished combustible wall

Non-Combustible material

Non-combustible

decorative facing

(up to full brick depth)

Tile, stone or other

non-combustible material

Hearth

Refractory

2 x 4 header, flush with

front of stand-offs

2 x 4 stud wall

Figure 12.10 Decorative Facing

Note: We recommend mortar be applied after

facing materials are installed. Refer to Sec-

tion 11.G.

Heatilator • Birmingham BIR42-B • 4059-681C • 9/12