3-7. PROGRAMMING

The holding temperature can be changed at this time by

(Continued)

using . Factory setting for air temperature is 37ºF (3ºC)

in the Chilling Mode and 0ºF (-18ºC) in the Freezing Mode.
The minimum temperature setting is 32ºF (0ºC) in the Chilling
Mode and -31ºF (-35ºC) in the Freezing Mode. The maximum
is 50ºF (10ºC) in the Chilling Mode and 32ºF (0ºC) in the
Freezing Mode.

Maximum duration of De-icing Cycle (minutes). Press
7 times and the digital display shows the time duration of
the De-icing Cycle. The factory setting is 25 minutes, but this
can be changed to a maximum setting of 60 or a minimum of
25 by using .

Evaporator temperature for the end of De-Icing Cycle.
Press 8 times and the digital display shows the evapo-
rator temperature at which the controls automatically turn off
the De-icing Cycle. The factory setting is 77ºF (25ºC), but this
can be changed to a maximum setting of 104ºF (40ºC) or the
minimum of 50ºF (10ºC) by using .

Temperature differential before high air temperature
alarm.
Press 9 times and the digital display shows the
number of degrees, above the holding temperature, at which an
alarm sounds, indicating the hold temperature is too high.

The factory air temperature setting is 27ºF (-3ºC), but can
be changed to a maximum setting of 54ºF (12ºC) or a
minimum temperature of 7ºF (14ºC) by pressing .

Temperature differential before low air temperature
alarm.
Press 10 times and the digital display shows
the number of degrees below the holding temperature, at which
an alarm sounds, indicating the hold temperature is too low.

The factory air temperature setting is 27ºF (-3°C), but can
be changed to a maximum setting of 54ºF (12°C) or a mini-
mum of 18ºF (-8°C) by pressing .