OM-493 Page 18

SECTION 6 – OPERATING AUXILIARY EQUIPMENT

6-1.

Standard Receptacles

Ref. ST-192 519 -A

Y

If unit does not have GFCI re-
ceptacles, use GFCI-
protected extension cord.

.

Auxiliary power decreases as
weld current increases.

Set Fine Adjust control R1 at 10
for full auxiliary power.

1

240 V 30 A AC Receptacle
RC1

RC1 supplies 60 Hz single-phase
power at weld/power speed. Maxi-
mum output is 7.2 kVA/kW.

2

120 V 20 A AC Duplex
Receptacle RC2

3

120 V 20 A AC Duplex
Receptacle RC3

RC2 and RC3 supply 60 Hz single-
phase power at weld/power speed.
Maximum output from RC2 or RC3
is 2.4 kVA/kW.

4

Circuit Breakers CB1 and
CB2

CB1 and CB2 protect RC1 from
overload. If CB1 or CB2 opens,
RC1 does not work. 120 volts may
still be present at RC1.

5

Circuit Breaker CB3

6

Circuit Breaker CB4

CB3 protects RC2 and CB4 pro-
tects RC3 from overload. If a circuit
breaker opens, the receptacle does
not work.

.

Press button to reset circuit
breaker. If breaker continues to
open, contact Factory
Authorized Service Agent.

Combined output of all receptacles
limited to 8.5 kVA/kW rating of the
generator.

EXAMPLE: If 20 A is drawn from
each 120 V duplex receptacle, only
13 A is available at the 240V
receptacle:

2 x (120 V x 20 A) + (240 V x 15 A)
= 8.4 kVA/kW

7

Auxiliary Power While
Welding Label

4

5

6

1

S-166 360-A

See Owner’s Manual for additional information.

Weld Current

In Amperes

Total Power

120V

210

140

90

1000

4300

6000

36

50

8

240V

18

25

4

WITH FINE ADJUST SET AT 10

In Watts

Receptacle

Receptacle

SIMULTANEOUS WELDING AND POWER

7

Amperes

Amperes

2

3