Hoshizaki KM-1601SWH/3 User Manual

Page 31

Advertising
background image

31

b) Connection to a Closed Loop System
• Condenser water supply inlet is 1/2" female pipe thread (FPT). A minimum of 3/8" nominal

ID copper water tubing or equivalent is required for the condenser water supply line.

• Condenser return outlet is 3/8" FPT. A minimum of 3/8" nominal ID copper water tubing or

equivalent is required for the condenser return line.

• Shut-off valves and drain valves should be installed at both the condenser water supply

inlet and condenser return outlet.

• The water supply to the condenser should not drop below 4 GPM.
• The pressure differential between the condenser water supply inlet and condenser return

outlet must be no less than 10 PSIG.

• When using a glycol blend, the solution mixture should be less than 30% glycol.
• In order to maintain the proper high side pressure, the condenser water supply inlet

temperature should not drop below 45°F (7°C) and the condenser return outlet
temperature must be in the 104°F to 115°F (40°C to 46°C) range. Once the icemaker
installation is complete, confirm the condenser return outlet temperature 5 minutes after a
freeze cycle starts. If the condenser return outlet temperature is not in the proper range,
use a flat blade screwdriver to rotate the adjustment screw on the water-regulating valve
until the temperature is in the proper range (rotate counterclockwise to raise temperature
or clockwise to lower temperature).

Condenser

Return Outlet

3/8" FPT

Condenser

Return Line

Shut-Off Valve

Condenser Return

Line Drain Valve

Fig. 19

KM-1601SWH/3

Connection to a Closed Loop System

Separate piping to approved drain.

Leave a 2-inch (5-cm) vertical air

gap between the end of each pipe

and the drain.

Icemaker Water

Supply Line

Shut-Off Valve

Icemaker Water Supply

Line Drain Valve

Icemaker

Icemaker Water

Supply Inlet

1/2" FPT

Bin Drain Outlet

3/4" FPT

2-inch (5-cm)

air gap

Floor Drain

Icemaker

Drain Outlet

3/4" FPT

Bin

Condenser Water

Supply Line

Shut-Off Valve

Condenser Water Supply

Line Drain Valve

Condenser

Water Supply

Inlet 1/2" FPT

Vent Tube

Minimum 3/8" Nominal

ID Copper Water Tubing

Minimum 3/4"

Nominal ID Hard Pipe

Condensation

Drain Outlet

3/8" OD Hard

Tube

Vent Tube

Minimum 3/8"

Nominal ID Copper

Water Tubing