Pre-installation checks, Riva 76 – Stovax PM235 RV66AVC User Manual

Page 20

Advertising
background image

20

2.1 Additional ventilation is required to comply with the

requirements of the Building Regulations. This must be

provided using a permanently open air vent, of the size

listed, which is positioned so that it is not liable to be

blocked both inside and outside the building.

2.2 Extractor fans or cooker hoods must not be placed in the

same room or space as this can cause the appliance to emit

fumes into the room.

2.3 If any of these checks reveal problems do not proceed

with the fitting of the appliance until they have been

rectified.

2. ADDITIONAL VENTILATION

PRE-INSTALLATION CHECKS

mm2

NONE

1650mm2 1650mm2 1650mm2 2475mm2

Additional Ventilation cm2

NONE

16.5cm2

16.5cm2

16.5cm2 24.75cm2

in2

NONE

2.56in2

2.56in2

2.56in2

4.00in2

Riva

40

Riva

55

Riva

66

Riva

66

Avanti

Model
Riva 40-RV 40/RV40B
Riva 55-RV 55/RV55B
Riva 66-RV 66/RV66B
Riva 66 Avanti-RV66 AVC
Riva 66-RV76/RV76B

Riva

76

Advertising
This manual is related to the following products: