Electrical connections , 40, Installation instructions, Caution – GE 49-85179 User Manual

Page 39: Electrical connections

Advertising
background image

Installation Instructions

39

ElECTRICAl ConnECTIonS

Electrical Requirements

120-volt, 60 Hertz, properly grounded branch circuit

protected by a 15-amp or 20-amp circuit breaker

or time-delay fuse.

Extension Cord Cautions

Because of potential safety hazards associated with certain

conditions, we strongly recommend against the use of

an extension cord. However, if you still elect to use an

extension cord, it is absolutely necessary that it be a

UL-listed, 3-wire grounding-type appliance extension cord

and that the current carrying rating of the cord in amperes

be equivalent to, or greater than, the branch circuit rating.

Grounding

IMPoRTAnT—(Please read carefully)
FoR PERSonAl SAFETy, THIS APPlIAnCE MUST

BE PRoPERly GRoUnDED.

The power cord of this appliance is equipped with a

3-prong (grounding) plug which mates with a standard

3-prong grounding wall receptacle to minimize the

possibility of electric shock hazard from this appliance.
The customer should have the wall receptacle and circuit

checked by a qualified electrician to make sure the

receptacle is properly grounded.
Where a standard 2-prong wall receptacle is encountered,

it is the personal responsibility and obligation of the

customer to have it replaced with a properly grounded 3-

prong wall receptacle.
Do noT, UnDER Any CIRCUMSTAnCES, CUT oR REMoVE

THE THIRD (GRoUnD) PRonG FRoM THE PowER CoRD.
A word about GFCIs – GFCIs are not required or

recommended for gas range receptacles.
Ground Fault Circuit Interrupters (GFCIs) are devices that

sense leakage of current in a circuit and automatically

switch off power when a threshold leakage level is detected.

These devices must be manually reset by the consumer.

The National Electrical Code requires the use of GFCIs in

kitchen receptacles installed to serve countertop surfaces.

Performance of the range will not be affected if operated

on a GFCI-protected circuit but occasional nuisance tripping

of the GFCI breaker is possible.

3

ElECTRICAl ConnECTIonS

(ConT.)

A. Usage Situations where Appliance Power Cord will

Be Disconnected Infrequently.

An adapter may be used only on a 15-amp circuit.

Do not use an adapter on a 20-amp circuit. Where local

codes permit, a TEMPoRARy ConnECTIon may be

made to a properly grounded 2-prong wall receptacle by

the use of a UL-listed adapter, available at most hardware

stores. The larger slot in the adapter must be aligned

with the larger slot in the wall receptacle to provide

proper polarity in the connection of the power cord.

When disconnecting the power cord from the adapter,

always hold the adapter with one hand. If this is not done,

the adapter ground terminal is very likely to break with

repeated use. Should this happen, Do noT USE the

appliance until a proper ground has again been

established.

3

Preferred Method

Ensure proper ground
exists before use

Temporary Method

(Adapter plugs not permitted in Canada)

Ensure proper ground
and firm connection
before use

Align large prongs/slots

CAUTIon:

Attaching the adapter ground

terminal to the wall receptacle cover screw does not

ground the appliance unless the cover screw is metal,

and not insulated, and the wall receptacle is grounded

through the house wiring. The customer should have

the circuit checked by a qualified electrician to make

sure the receptacle is properly grounded.

Advertising