Notes on the network settings:

(a) In the example only one servo amplifier is connected to the CC-Link network. This value must

be increased by the number of slave stations installed if applicable.

(b) These values specify which bits or data words are to be used to control the servo amplifier.

The settings shown in the example are for the following assignments:

(c) Slave station type setting:

Connect the PC to the PLC and transfer the modified project to the controller.

NOTE

If the CC-Link connection to the servo amplifier is established successfully the L.RUN, SD
und RD status LEDs on the servo amplifier will light up.

CC-Link Communication Settings

Positioning via a CC-Link Network

5 - 36

MITSUBISHI ELECTRIC

Fig. 5-7:

This configuration also enables exchange of data words

PLC -> Servo Amplifier

Servo Amplifier -> PLC

PLC I/Os

Registers

Signals

PLC I/Os

Registers

Signals

Y100

RYn0

SON

X100

RXn0

RD

Y101

RYn1

ST1

X101

RXn1

INP

Y102

RYn2

ST2

X103

RXn3

ZP

Y103

RYn3

DOG

X11A

RX(n+1)A

ALM

Y104

RYn4

LSP

Y105

RYn5

LSN

NOTE:

Signals DI5, DI6 and DI7 are only available
when the amplifier is configured to occupy 2
stations in the network.

Y106

RYn6

MD0

Y10A

RYnA

DI0

Y10B

RYnB

DI1

Y10C

RYnC

DI2

Y10D

RYnD

DI3

Y10E

RYnE

DI4

Y10F

RYnF

RES

Table 5-1: Signal assignments