Ss38 direct vent gas stove, Venting installation information, Fp1951 termination clearances – Monessen Hearth SS38 User Manual

Page 12

Advertising
background image

46D0232

12

SS38 Direct Vent Gas Stove

TERMINATION CLEARANCES FOR BUILDINGS WITH COMBUSTIBLE
AND NONCOMBUSTIBLE ExTERIORS

NOTE: Any vent
configuration within
the shaded areas is
acceptable.

VENTING INSTALLATION INFORMATION

Figure 7 -
Allowable Venting Chart

V

G

G=6" (152mm)

F

F=6" (152mm)

V

V

G

G = Combustible 24"(610mm)
 

Noncombustible 18"(457mm)

Combustible & 
Noncombustible
H = 24" (610mm)
J =  20" (508mm)

V

H

J

C = Maximum depth of 48" (1219mm)
    for alcove location
D = Minimum width for back wall of
    alcove location
    Combustible - 38" (965mm)
    Noncombustible - 24" (610mm)
E = Clearance from corner in alcove 
    location
    Combustible - 6" (152mm)
    Noncombustible - 2" (51mm)

E

V

D

C

C

Inside Corner 

Alcove Location

Outside Corner 

Balcony with No Side Wall

Balcony with Perpendicular

Side Wall

FP1951
termination clearances

FP1951

  2

4

6

8

10

12

14

16

18

20

22

24

26

28

30

32

34

36

38

40

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

47.5"

(121cm)

ST1102
VS38 vent graph

V

ertical Height 40' (12.2 m) Max.

Horizontal run 20' (6 m) Max.

ST1102