Ss38 direct vent gas stove, Venting installation, Fp1955 horizontal vent cap – Monessen Hearth SS38 User Manual

Page 14: Warning, Fp1956 vinyl siding standoff, Fp1957 install firestop, Do not recess vent terminal into a wall or siding

Advertising
background image

46D0232

14

SS38 Direct Vent Gas Stove

VENTING INSTALLATION

4. Apply a bead of non-hardening mastic around the

outside edge of vent cap. Position the vent cap in the
center of the 7Z\x" (190 mm) or 9Z\x" (241 mm) hole on the
exterior wall with the word “UP” on the vent cap facing
up. Insure proper clearance of 1" to combustibles is
maintained. Attach the vent cap with four wood screws
supplied. Figure 12.

NOTE: Replace the wood screws with appropriate fasteners
for stucco, brick, concrete, or other types of siding.

VO584-100
Vent Opening
2/99 djt

Vent Opening for Combustible Walls

9B\,”

(244 mm)

Min.

Stove Hearth

Framing Detail

Opening for Noncombustible Wall

7Z\x”

(190 mm)

Stove Hearth

FP2293

Figure 11 -
Vent Opening Requirements

9B\,”

(244 mm) Min.

HOT

FP1955
horizontal vent cap

Vent Cap

Wood Screw

Apply Mastic to
All Four Sides

FP1955

Figure 12 -
Install Horizontal Termination

W

ARNING

Do not recess vent terminal into a wall or
siding.

For vinyl siding, stucco, or wood exterior use vinyl siding
standoffs between vent cap and exterior wall. The vinyl
siding standoff prevents excessive heat from melting the
vinyl siding material. Bolt the vent cap to the standoff. Apply
non-hardening mastic around outside edge of the standoff
instead of the vent cap assembly. Use wood screws pro-
vided to attach the standoff. Figure 13

HOT

FP1956
vinyl siding standoff

Cut Vinyl Siding
Away to Fit
Standoff

Standoff

Apply
Mastic to
All Four
Sides

Nut

Wood Screw

Bolt

Termination

FP1956

Figure 13 -
Install Vinyl Siding Standoff and Termination

5. Slide the wall thimble over the vent pipe before con-

necting the horizontal run to the vent cap. Figure 14

6. Carefully move the stove with vent assembly attached

toward the wall and insert the vent pipe into the hori-
zontal termination. The pipe overlap should be a mini-
mum of 1Z\v" (32 mm). Apply silicone to the outer pipe
connection. Fasten all vent connections with screws
provided.

7. Slide the wall thimble against the interior wall surface

and attach with screws. Figure 14

FP1957
install firestop

Interior Wall
Surface

Firestop

Vent Cap
(Horizontal
Termination)

Screw

Horizontal
Vent Pipe

FP1957

Figure 14 -
Install Firestop on Horizontal Vent Pipe