VERTICAL TERMINATION CONFIGURA-
TIONS

Figures 23 through 26 show four different configurations
for vertical termination.
IMPORTANT: You must install a restrictor on all vertical
installations.

Figure 23 -
Vertical Rigid Venting Configuration Using Two
90° Elbows

NOTE: Install restrictor into 4" collar of stove or first vent
section as shown.

NOTE: Install restrictor
into 4" collar of stove
or first vent secton as
shown.

VENTING INSTALLATION

Figure 21 -
Cathedral Ceiling Support Box Installation

ST1108
cat clg support box

Level

Cathedral Ceiling
Support Box

2" Minimum Below
Finished Ceiling

Cut Hole 1/8"
Larger than
Support Box
when Projected
onto Roofline.

ST1108

ST1109
installed support box

Figure 22 -
Installed Cathedral Ceiling Support Box

Apply Non-hardening
Mastic Under all Edges of
Support Box before Nailing

ST1109

H  

V

ST1110
vert term no 1 elbow

Table 5 - Vertical Venting with Two (2) 90° Elbows

Vertical (V) Minimum

Horizontal (H) Maximum

8'

2'

9'

4'

10'

6'

11'

8'

23'

8'

ST1110