Fp2371 gas connect, Fp2499 manual valve – Monessen Hearth EYF18 User Manual

Page 12

Advertising
background image

65D1009

1

EYF Series Unvented Gas Log Set

NOTICE: A qualified gas appliance installer must connect
the heater to the gas supply. Consult all local codes.
IMPORTANT: Hold heater valve firmly with a wrench to
prevent movement when connecting to inlet pipe.
Always use an external regulator for all propane/LPG
heaters and high pressure one to two-pound systems
only
, to reduce the supply tank pressure to a maximum of
13" w.c. This is in addition to the internal regulator in the
heater valve.

GAS LINE CONNECTION

W

ARNING

Use new black iron or steel pipe. Internally tinned copper or copper tubing can
be used per National Fuel Code, section 2.6.3, providing gas meets hydrogen
sulfide limits, and where permitted by local codes. Gas piping system must be
sized to provide minimum inlet pressure (Listed on Data Plate) at the maximum
flow rate (BTU/Hr). Undue pressure loss will occur if the pipe is too small.
A manual shutoff valve must be installed upstream of the appliance. Union tee
and plugged 1/8" NPT pressure tapping point should be installed upstream of
the appliance. Figure 13

FP2371
gas connect

Stainless
Flexible
Tube

Pipe

Possible Locations
for Pressure
Tapping Point

Gas
Supply
Inlet

To
Heater
Valve

Pipe
Coupling

Manual Shutoff
Valve

FP371

Figure 13 -
Gas Connection

CHECk GAS TYPE: The gas supply must
be the same as stated on the heater’s rat-
ing plate. If the gas supply is different, DO
NOT INSTALL THE HEATER. Contact your
dealer for the correct model.

Connecting directly to an unregulated
propane/LPG tank can cause an explo-
sion.

W

ARNING

W

ARNING

The heater gas inlet connection is a 3/8" NPT at the valve.
All units have the inlet connection on the right side, when
you face the unit. To connect from the opposite side, route
the pipe under the rear portion of the unit.
When tightening up the joint to the valve, hold the valve
securely to prevent movement.

MANUAL CONTROL

Figure 14
The pressure regulator is preset and locked to dis-
courage tampering.
If the pressure is not as specified,
replace the regulator with the correct part from the parts
list in this manual.

Remove 1/8" NPT plug, locat-

ed on side of regulator body.

Install fitting and tubing to

pressure gauge. After

taking pressure reading,

reinstall test plug.

Check for gas

leaks.

FP2499
manual valve

NPT Test Plug

FP499

Figure 14 -
Pressure Test Point Location for
Manual Control

MILLIVOLT CONTROL

Figure 15
The valve regulator con-
trols the burner pressure
which should be
checked at the pres-
sure test point.
Turn captured screw
counter clockwise two
or three turns and
then place tubing to
pressure gauge over
test point (Use test
point “OUT” closest
to control knob). Af-
ter taking pressure
reading, be sure and turn captured screw clockwise firmly
to re-seal. Do not over torque. Check for gas leaks.

Figure 15 - Pressure Test Point Location
Millivolt Control

FP2372
millivolt valve

Test Port "OUT"

FP37