EYF Series Unvented Gas Log Set

INSTALLATION

Heat resistant material (minimum requirements) with
wooden mantel or other combustible projection:
To
install the heater with a wooden mantel, shelf or other
combustible projection above, first measure the heat
resistant material shown in Figure 6, then refer to Table
B.

FP2532
mantel clear w hood

8" or More of Heat
Resistant Material

Hood

Heater in
Fireplace or
Firebox

FP53

Figure 6 -
Mantel Clearance with Hood

EYF24/18 Requirements

for Safe Installation with

Heat Resistant Material Wooden Mantel, Shelf or

Measurement

Other Combustible

Projection

0" or more

Hood not required. Figure 6

8" to less than 0"

Install hood (CABR/CABL)

and refer to Figure 7; OR

extend heat resistant material

to at least 1" and refer to

Figure 8.

Less than 8"

Extend heat resistant material

to at least 8" and install hood

(CABR/CABL), refer to

Figure 6. OR, extend heat

resistant material to a height

of at least 1" and refer to

Figure 8.

Table B -
Heat Resistant Material Heights and Mantel Location

8” 

Min

13”

18”

20”

256O”

6” - 10”

12”

FP2534
Min. mantel w hood

Heat
Resistant
Material

Hood

Heater in Fireplace
or Firebox

FP534

Figure 7 -
Minimum Mantel Clearance with Hood

Example: A mantel may project from the wall a maximum
of Z\x" at a minimum of 13" above the opening and a
maximum of 10" at a minimum of 18" above the open-
ing.

20”

Min.

32”

10” or Less

FP2535
min mantel no hood

Heat
Resistant
Material

Heater in Fireplace
or Firebox

FP535

Figure 8 -
Minimum Mantel Clearance with No Hood

Example: The bottom of the mantel may project from the
wall a maximum of 10" at a minimum of 3" above the
opening.