MGE UPS Systems 66102 User Manual

Page 22

Advertising
background image

T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R

Network Management Card – User Manual

34003991EN/GA

- 22 -

The first shutdown criteria initiates the restart of the

shutdown sequence

.

Z

If remaining time is under (0 to 99999 seconds, 180 by default) is the minimum remaining backup time from which the shutdown

sequence is launched.

Z

If battery capacity is under (0 to 100%); this value cannot be less than that of the UPS and is the minimum remaining battery

capacity level from which the shutdown sequence is launched.

Z

Shutdown after (0 to 99999 minutes, not validated by default) is the operating time in minutes left for users after a switch to backup

before starting the shutdown sequence.

Z

Shutdown duration (120 seconds by default) is the time required for complete shutdown of systems when a switch to backup time

is long enough to trigger the shutdown sequences. It is calculated automatically at the maximum of Shutdown duration of

subscribed clients but can be modified in the Advanced mode.

Z

If battery capacity exceeds Minimum battery level to reach before restarting the UPS after utility restoration

.

Important: Certain UPSs do not support this option

For the controlled outlets ("group 1 or group 2" by default)

The page enables programming of operation time and level in backup mode to manage outlet load shedding in the event of electric power

failure:

Z

Switch Off after (from 0 to 99999, 65535 by default) defines the time during which the outlet is supplied starting from the moment

of utility failure. Caution, this time includes the outlet shutdown duration.

Z

Switch Off if battery capacity under (0 by default) is an extra condition for outlet shutdown that can trigger the shutdown

sequence before the shutdown duration runs out.

Z

Shutdown duration is the time required for complete shutdown of the systems supplied by the outlet when an outlet shutdown

sequence is launched.

It is calculated automatically using the maximum shutdown durations of notified applications on the outlets.

Z

Switch On after (from 0 to 99999, default 65535) is the period between main output startup and startup of the relevant

programmable outlet, therefore outlet startup can be delayed in relation to the main output.

Important: Certain UPSs do not support this option

Export settings to file: Enables exportation ("Download" button) and saving of card configuration information.

Import settings from file: Enables selection of a configuration file ("Browse" button) and uploading ("Upload" button) of card configuration

information

Security: The administrator has to click on Save and enter his/her login/password to save any modifications. The login and password by

default are: MGEUPS