T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R

Network Management Card – User Manual

34003991EN/GA

- 46 -

5 Server protection

5.1 Set-up of the shutdown parameters

The Network Shutdown Module, on protected server boot, subscribes itself automatically to

notified applications

list and sends its essential

data:

Z

IP Address or hostname of the server on which it is installed: So that the card can inform it of power events.

Z

Time required to shutdown the server (Shutdown Duration, configurable in the "Set-up" menu of each NSM): The card takes into account

the longest shutdown time of all the Network Shutdown Modules subscribed (This is the Shutdown duration of the

Shutdown parameters

)

page to manage UPS shutdowns without affecting any of Shutdown Modules connected.

During normal operation, the Network Shutdown Module periodically checks its connection with the card.

In case of a major power event, the card sends information to the Network Shutdown Module which reacts according to the situation.

(shutdown order, programmed actions, messages to the administrator and to users via the network)

When the server shuts down, the Network Shutdown Module unsubscribes itself from the

notified applications

.

5.1.1 Shutdown criteria managed by the Network Management Card

During an extended power failure, three criteria may cause the server shutdown procedure to be initiated. If several criteria are selected, (See

page

Shutdown parameters

), the first criterion encountered will launch the shutdown procedure.

At the end of the shutdown procedure, when all servers have been shut down, the UPS may shut down to avoid unnecessary discharge of its

batteries, depending on its configuration.

Start of the shutdown sequence

Delay before

shutdown

Utility failure

Remaining autonomy

100%

Shutdown after :

If remaining time under

UPS Shut off

Card parameters

UPS parameters

Shutdown duration

Battery

capacity

0%

Shutdown if

remainig

capacity under

t