Configuration, Administration, Network – MGE UPS Systems 66102 User Manual

Page 8: List of ports used, Environment sensor, 3 configuration, 4 administration, 5 network, 6 environment sensor, 1 list of ports used

Advertising
background image

T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R

Network Management Card – User Manual

34003991EN/GA

- 8 -

Z EMC: 89/336/EEC and 93/68/EEC.

1.3.3 Configuration

The user can configure the card with one of the following means:

Z

Web browser

Z

Local serial link (network parameters)

Z

BOOTP/DHCP (network parameters)

1.3.4 Administration

Z

Up to 50 workstations protected by Network Shutdown Modules - Central or local configuration.

Z

Up to 5 browsers connected at the same time (3 in SSL).

Z

Minimum recommended browser versions: Internet Explorer 6.x, Mozilla Firefox 1.5, Netscape 6.x

Z

E-mail sending configurable according to UPS alarms and transmission of a periodical report.

Z

Control of UPS on/off switching via the HTML interface.

Z

Adjustment and control of PowerShare outlets via the HTML interface, sequential starting of the installation and optimisation of backup

time by shutting down non-priority systems.

Z

Automatic data and time adjustment via NTP server.

Z

Protection by encrypted password.

Z

Protection by secure SSL connection.

Z

Saving of logs in the non-volatile memory.

Z

Languages available: English / French / Spanish / German / Italian

Z

On-line help in English available for each page.

Z

Card firmware updated via the network

1.3.5 Network

Z

Fast ETHERNET 10/100 Mbits compatibility with auto-negotiation on the RJ45 outlet

1.3.5.1 List of ports used

Z

BootP, DHCP

UDP 68 , 67

Z

HTML

TCP 80

Z

SSL

TCP 443

Z

NSM connection

TCP 5000

Z

SMTP 25

Z

NTP

123

Z

SNMP V1

161

Z

TRAP SNMP

162

1.3.6 Environment sensor

Z

Temperature measurement from 0 to 70°C with +/- 1°C accuracy

Z

Measurement of humidity from 0 to 100% with +/- 6% accuracy

Z

Min / max time-stamped function for temperature and humidity

Z

Choice of temperature readings in Celsius or Fahrenheit

Z

High and low thresholds, hysteresis and offset adjustable via Web interface

Advertising