T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R

Network Management Card – User Manual

34003991EN/GA

- 49 -

5.2 The different server and UPS shutdown sequences

5.2.1 Extended power outage, shutdown initiated by the Shutdown Timer (Shutdown after)

During battery backup time, the Shutdown Timer of the Network Management Card is reached: After a user-defined backup time period

(

Shutdown parameters

page), the shutdown of all servers is initiated, followed by the UPS shutdown (depending on its configuration). The

UPS restarts when utility power is restored (depending on its configuration)

Shutdown duration: Maximum value of shutdown times of the Network Shutdown Modules subscribed to the card. This value is updated

each time a client subscribes/ unsubscribes.

Start shutdown main

output

Utility failure

Utility

Shutdown after:

NSM 2 on output 1

NSM 1 on main

output

Shutdown duration

main output

Main output

Utility restore

Start shutdown

output 1

Output 1

Shutdown

duration output 1

Shutdown after 1:

5.2.2 Extended power outage, shutdown initiated by the "Low battery power" message

When the "Low battery power" criterion is displayed, the UPS is shut off after taking into account the shutdown duration of the servers.

"Low battery power": The message appears if either of the two following criteria is checked:

- Low Battery Level

- Low Battery Delay