Network Management Card – User Manual

34003991EN/GA

- 9 -

Z

Possibility of notification of status changes by e-mail, SMS or SNMP trap

Z

Position detection of 2 dry contacts (maximum sensor/contact distance: 20 m)

Z

Name and status of each configurable contact

Z

Recording of events and measurements in the card log

Z

Possibility of shutting down the installation in the event of a threshold being exceeded or on opening / closure of a dry contact

Z

Connection to the card with straight CAT5 RJ45 network cables (maximum card/sensor distance: 20 m)

Z

Hot installation

1.3.7 MIB (Management Information Base)

Z

Compatible with MIB MGE V1.7

The list of objects managed can be found in the

appendix

1.3.8 Default parameters

Function

Parameter

Default value

Possible value

Network

IP address

172.17.16.16

Network IP address

Subnet mask

255.255.0.0

Network IP address

Gateway Address

0.0.0.0

Network IP address

BOOTP/DHCP

Enabled

Active / Deactivated

Firmware Upload

Enabled

Active / Deactivated

SMTP server

smtpserver

31 characters maximum

System

UPS Contact

Computer Room Manager

49 characters maximum

UPS Location

Computer Room

49 characters maximum

History log interval (sec.)

60

5 to 99999 sec.

Environment log interval (sec.)

300

60 to 99999 sec.

Default Language

English

English / French / Spanish /

German / Italian

Manager table

empty

50 maximum

Access control

User name

MGEUPS

10 characters maximum

Password

MGEUPS

10 characters maximum

Community name read

public

49 characters maximum

Trap port

161

Non configurable

Date and time

Date and time adjustment

Synchronise with an NTP server

Synchronise with an NTP server

Synchronise manually

NTP server

pool.ntp.org

49 characters maximum

Serial link

Speed

9600 baud

Non configurable

Data bits

8

Non configurable

Stop bits

1

Non configurable

Parity

without

Non configurable

Flow control

without

Non configurable