VENT INSTALLATION

BELOW GRADE INSTALLATIONS

When it is not possible to meet the required vent terminal clearances of 12" above grade level, a snorkel kit is recommended.

It allows installation depth down to 7" (178mm) below grade level. The 7" (178mm) is measured from the center of the

horizontal vent pipe as it penetrates through the wall.
Ensure that sidewall venting clearances are observed. If venting system is installed below ground, we recommend a
window well with adequate and proper drainage to be installed around the termination area.
If installing a snorkel, a minimum 24" vertical rise is necessary. The maximum horizontal run with the 24” vertical pipe is

36". This measurement is taken from the collar of the fireplace (or transition elbow) to the face of the exterior wall. See the

Sidewall Venting Graph for extended horizontal run if the vertical exceeds 24".
1. Establish vent hole through the wall. See Figure 20, page 21.
2. Remove soil to a depth of approximately 16" below base of snorkel. Install drain pipe. Install window well (not supplied).

Refill hole with 12" of coarse gravel leaving a clearance of approximately 4" below snorkel. See Figure 31.

3. Install vent system.
4. Ensure a watertight seal is made around the vent pipe coming through the wall.
5. Slide the snorkel into the vent pipes and secure to the wall.
6. Level the soil so as to maintain a 4" clearance below snorkel. See Figure 31.

• Do not back fill around snorkel.
• A clearance of at least 4" must be

maintained between the snorkel and
the soil.

W

ARNING

If the foundation is recessed, use recess brackets (not supplied) for securing lower portion of the snorkel. Fasten brackets to

wall first, then secure to snorkel with self drilling #8x

1

/

2

sheet metal screws. It will be necessary to extend vent pipes out as

far as the protruding wall face. See Figure 32.

Figure 32 - Snorkel Installation,

Recessed Foundation

Figure 31 - Below Grade Installation

Screws

Minimum

4" Clearance

Ground

Window Well

Gravel
Drain

Foundation Wall

Firestop

24"

Minimum

Foundation

Recess

Watertight Seal

Around Pipe

Sheet Metal

Screws

Wall Screws

Snorkel