3 electrical specificati, 1 dc input 1-3, 2 ac output (per module – MGE UPS Systems 3.5 to 21 kVA N+1 User Manual

Page 15: Electrical specifications -3, Dc input -3, Ac output (per module) -3, Inverter module dimensions -3, Owner’s manual

Advertising
background image

Introduction

page 1 — 3

Owner’s Manual

Table 1-2: Inverter Module Dimensions.

Inverter Module

HEIGHT (in/cm)

DEPTH (in/cm)

WIDTH (in/cm)

WEIGHT (lb/kg)

64004-9MSK1

5.18 / 13.16

15.12 / 38.4

15.76 / 40.03

46 / 20.86

Note: Weight: Six-mod receiver = 135 lbs. (61.2 kg) 1 UPS Module = 46 lbs. (20.09 kg)

Total System Weight, 21 kVA system = 411 lbs. (186.4 kg)

1.3

Electrical Specifications

Electrical Specifications are subject to revision without notice.

1.3.1

DC Input

Nominal: -48Vdc; Operating Range: -39.5Vdc to -57 Vdc

NOTE:

An external DC circuit breaker or fuse should be used at the DC
source.

1.3.2

AC Output (per module)

Voltage:

120Vrms

or

240Vrms

Current:

25Arms

or

12.5Arms

Frequency:

60Hz

or

50Hz

Ta b l e 1 - 3 : S 4 A C O u t p u t C u r r e n t R a t i n g s .

Attention: Watts rating = 85% of the VA rating at 120/240 VAC.

MAXIMUM OUTPUT RATINGS

7 KVA unit

14 KVA unit

21 KVA unit

Vout Iout

Output

Output

Iout Output

Output

Iout Output

Output

(Vac)

(A)

Power

VA

(A)

Power

VA

(A)

Power

VA

(W)

(VA)

(W)

(VA)

(W) (VA)

110

58.33

6000

6416

116.66

12000

12833

175

18000

19250

115

58.33

6000

6708

116.66

12000

13416

175

18000

20125

120

58.33

6000

7000

116.66

12000

14000

175

18000

21000

208

29.165

6000

6066

58.33

12000

12133

87.5

18000

18200

220

29.165

6000

6416

58.33

12000

12833

87.5

18000

19250

230

29.165

6000

6708

58.33

12000

13416

87.5

18000

20125

240

29.165

6000

7000

58.33

12000

14000

87.5

18000

21000

Units configured to other then 120/240VAC are derated due to current limit.
The % Load reading on the display panel is always with reference to the 120/240 Vac WATT and VA ratings.

Advertising