3 dc input circuit b, 3 line to neutral inverte, Dc input circuit breaker -5 – MGE UPS Systems 3.5 to 21 kVA N+1 User Manual

Page 23: Dc input circuit breaker -12, Line to neutral inverter receiver junction box -5, Static switch section - input and output wiring -6, Line to line inverter receiver junction box -12

Advertising
background image

Installation & Operation - Line to Neutral

page 2 — 5

Owner’s Manual

2.5.2 DC Input

Normal: -48VDC

Operating Range: -39.5 VDC to -57VDC

This system is designed for battery systems with the positive terminal Earth Ground. All DC breakers are

in the negative DC lines. The system DC terminals are isolated from Earth Ground.

2.5.3 DC Input Circuit Breaker

Due to tremendous amounts of short circuit current available (in excess of 1000A for as long as several minutes!)

from bank(s) of batteries, that supply electrical power to inverter systems, it is extremely important to connect a

properly sized DC circuit breaker at the DC input cable that feeds the inverter system. The following table is pro-

vided as a guide for selecting the proper circuit breaker.

Table 2-2: Line To Neutral Units Suggested DC Circuit Breaker Ratings.

Inverter rating

7 kVA

14 kVA

21 kVA

CB rating

200A

400A

600A

Figure 2-3: Line To Neutral Inverter Receiver Junction Box.

BATTERY

(-)

BATTERY

(+)

JUNCTION

BOX

INVERTER RECEIVER

WITH JUNCTION BOX

BACK VIEW

INVERTER RECEIVER

WITH JUNCTION BOX

SIDE VIEW

GND

L-IN

L-OUT

TB1

N-OUT

N-IN