5 environmental specific, 1 thermal dissipation 1, 6 safety approvals 1-5 – MGE UPS Systems 3.5 to 21 kVA N+1 User Manual

Page 17: Environmental specifications -5, Thermal dissipation -5, Safety approvals -5, Owner’s manual

Advertising
background image

Introduction

page 1 — 5

Owner’s Manual

1.5

Environmental Specifications

Operating Temperature

All models operate to specifications from -5°C to +50°C (+23°F to +122°F) for alti-

tude up to 3,300 feet (1006 Meters), and -5°C to 35°C (+23°F to + 95°F) for up

to 13,300 feet (4054 Meters).

Shipping Temperature

-40°C to +75°C (-40°F to +192°F) for shipping; Not recommended for storage.

Storage Temperature

-40°C to +60°C (-40°F to +166°F).

Operating Humidity

0 to 90% relative, without condensation.

Operating Altitude

200 feet below to 13,300 feet (4054 Meters) above sea level.

Audible Noise

Less than 59 dBA per Type 2, IEC and ANSI SI.4, when measured in a 40 dBA

environment at a distance of 4 feet from any surface.

Cooling

Cooling is by forced air. Air intake is through the front of the unit, exhaust out the

sides.

1.5.1

Thermal Dissipation

Heat rejection: 602.28 BTU/Hr for each rated KW of the inverter system. This is based on an inverter efficiency of

85% at full load and does not include load dissipation.

kVA rating

7

14

21

Watts

1059

2118

3177

BTU/Hr

3614

7227

10841

Est. A/C, TONS

0.301

0.602

0.903

1.6

Safety Approvals

Meets UL/CSA 60950 (listed) and European Standard EN60950.