3 unit kva rating id label, 4 on-line mode 2-15, 5 off-line mode 2-15 – MGE UPS Systems 3.5 to 21 kVA N+1 User Manual

Page 33: 7 line to line setup scre, Rack kva rating id label -10, On-line mode -10, Off-line mode -10, Connections -14, Ac input/output voltage selection -14, Software configuration set-up -14

Advertising
background image

Installation & Operation - Line To Line

page 2 — 15

Owner’s Manual

Figure 2-7: Line To Line Setup Screen.

After the selections are complete, click on the Save button. The data will be sent to the appropriate address in the

controllers “EEROM”. Remove the applied 48VDC to the system by turning off the main DC feed circuit breaker.

2.9.3 Unit kVA Rating ID Label

For kVA rating see the inverter ID label. Use the label kVA rating, regardless of the number of inverter modules
installed.

The processor will detect and display the number of modules installed and the number of modules that are “ON”
and operating without fault. MGE is offering the 7, 14, and 21 kVA rating.

2.9.4 On-Line Mode

On-line mode is the mode in which the load is powered by the inverter system, not the utility. It will get clean, tran-
sient free electrical power from the inverter system, which is producing the AC power from a DC power source. In
the event of inverter failure, the static transfer switch will transfer the load to the utility power if available.

2.9.5 Off-Line Mode

Off-line mode is the mode in which the load is powered from the Utility power line (external AC input power). In the
event of a power failure, a static transfer switch will connect the system output to the inverter and activate the invert-
er so as to provide continuous power to the load with no interruptions of power to the load.

x

?

Line To Line Inverter Configuration

Rack kVA rating

Utility

Inverter voltage

Mode

Inverter frequency

DC fail auto restart

Cancel

Save

7.0

14.0

21.0

Voltage connected

AC tree

On-line

Off-line

208

220

230

240

50 hz

60 hz